Plant, monitor and fault injector

rtl/control_plant_witness.sv is the vendor-neutral fabric entry point. Both sampled plants, reference generator, strict deadline monitor, fault injector and simultaneous-event capture feed the real dual-clock record FIFO. Tests drain binary records into the public host analyzer. This is simulation evidence; no physical board is available. C/Rust/RTL controllers and the closed fabric feedback path are specified in CONTROLLERS.md. Native CLI commands replay through simulated actuator transactions. Capture I/O registers and AXI transport are exercised against the actual plant in simulation; board processor service, vendor timing constraints, power readings and physical safe-state acceptance remain planned.

Ports and configuration

All inputs except drain_request are synchronous to capture_clock; drain inputs and outputs belong to drain_clock. run_reset_n asynchronously asserts the common run reset; each domain releases it after two local edges. A reset flushes events, plant state, monitor and injection. capture_active marks local reset release. control_cycle.sv owns the sample period, actuator register, command classification and event strobes. Hold configuration stable for the run.

Inputs Contract
enable, stop_after_cycle Start at cycle zero; hold enable high through the last cycle's deadline. Stop includes that deadline, with no extra sample. Reset before restarting.
sample_read First sample read per cycle produces SAMPLE_READ.
actuator_write, command_cycle, command_value Synchronous actuator command, signed Q8.24. Matching current-cycle writes strictly before its deadline satisfy it. Only the first such write produces ACT_WRITE; later timely writes may replace the actuator.
fault_arm, fault_kind, fault_cycle, fault_periods Arm one injection before its target sample. Kinds 0/1/2/3 are drop/delay/freeze/overload request. Positive duration required, target cannot be past or beyond the final cycle.
reference_mode, reference_amplitude, reference_offset, ramp_increment, phase_increment Step/ramp/sine selection 0/1/2; signed Q8.24 values, modulo-16 phase increment. Mode 3 uses zero amplitude plus offset.
drain_request Request next record; inspect data only with drain_valid.
Outputs Contract
sample_valid, cycle_number, sample_value, velocity, reference_value New registered sample/target on the update edge. Thermal velocity is zero.
actuator_value Latest accepted command; defined safe value wins on monitor trip and remains until reset.
sample_interrupt, delayed_interrupt, delayed_cycle Edge strobes; delayed origin survives coincident normal IRQ delivery.
safe_interrupt Latched trip indication, not a one-clock pulse.
run_finished, capture_quiescent Capture-domain final-deadline completion and completion with no remaining event group or event strobe. The latter does not imply the downstream FIFO or its receiver has drained. Both are also exposed by the fabric controller wrapper.
fault_ready, freeze_actuator, overload_request Injection availability and synchronous action levels. Readiness falls after trip or run completion; invalid schedule data is refused.
total_misses, consecutive_misses, late_commands Saturating 32-bit capture-domain counters; not coherent processor snapshots.
plant_clipped, reference_clipped Saturation at the last sample; retain/sample these with sample_valid. These are flags, not cumulative clipping counters.
counter_ticks, overflow_count, buffer_full Capture timebase, saturating combined lost-event count and downstream FIFO full status. Group queue exhaustion can lose events even when FIFO full is low.
drain_valid, drain_empty, drain_record Existing 16-byte stream in the drain domain.

Parameters: PERIOD_TICKS defaults to 100,000 at the planned 100 MHz (1 kHz); MISS_LIMIT defaults to three, must be positive; SAFE_VALUE defaults to zero. THERMAL selects the plant. ADDRESS_BITS is the existing FIFO width (1–14), and GROUP_ADDRESS_BITS is the simultaneous-event queue width (1–8, default six). Plant coefficients are compile-time signed Q8.24 parameters. Changing period requires recomputing them for that physical sample interval. Clock and period parameters do not qualify a physical oscillator or board rate.

Capture I/O registers

axi_control_witness.sv is the combined AXI peripheral: it connects the capture I/O and configuration registers to the actual plant and exposes its FIFO through the bus-domain record window. Its AXI addresses are offsets within an externally decoded 256-byte aperture. Plant coefficients and capture parameters retain the raw plant module's compile-time interface. Capture diagnostics and IRQ strobes belong to capture_clock; the record window, run_drained and retained interrupt_line belong to bus_clock. icicle_witness.sv is the board-facing AXI4-Lite boundary: it accepts the interconnect's 38-bit address and forwards the selected low eight bits to this peripheral. Its physical decode and retained interrupt route still require Libero validation. The processor/kernel interrupt mapping remains unqualified. External run_reset_n aborts AXI transactions as well as the run; quiesce the master before asserting it. The software run-bank reset below retains the AXI transport and its accepted responses.

control_io_registers.sv decodes capture-domain requests from axi_lite_clock_bridge.sv. Addresses are byte offsets within the peripheral. Only aligned 32-bit accesses are accepted. All writes require four byte strobes; unsupported accesses return AXI SLVERR without changing state.

Offset Access Contract
0x00 Read Return the current sample and snapshot its cycle, velocity, reference, time and miss count at the same capture edge. Refused while disabled or finished.
0x04 Read Bits 0–4: snapshot valid, run enabled, run finished, safe latched, capture quiescent.
0x08, 0x0c Read Read low timebase word at 0x08, then its latched upper word at 0x0c. Upper-word reads before an observation are refused.
0x10, 0x14, 0x18 Read Snapshot cycle, velocity and reference.
0x1c, 0x20, 0x24 Read Snapshot low time word, upper time word and total misses.
0x28, 0x2c Read/write Stage the command cycle and signed Q8.24 command value. Readback retains the last staged values.
0x30 Read/write Read the current capture/FIFO overflow count. Write 1 to commit both command stages; successful commit consumes both staging credits and emits one actuator-write strobe.
0x34 Read Current total deadline misses, including deadlines after the last sample read.

Snapshot fields are unavailable before the first successful sample read. Once captured, they remain unchanged across subsequent plant steps and run completion until another sample read or common reset. Timebase observation is independent of the sample snapshot. The SAMPLE_READ event retains the snapshot's capture-edge timestamp; AXI response arrival is a later event.

Commit is refused if either stage is missing, the run is disabled or finished, or safe state is latched. A successful bus response acknowledges the submitted transaction; the independent deadline monitor still determines timely acceptance and safe override. A mismatched command cycle remains subject to the plant's late-command contract. Reset invalidates snapshots, time observations and staging credits.

Run configuration registers

run_configuration_registers.sv holds the capture-domain run configuration. Writes require aligned full words. Configuration is immutable after a successful fault arm or start. Start is one-shot until common reset; writing zero cannot disable an active run or erase its deadlines. The sample period is read-only because the compiled plant coefficients declare that interval.

Offset Access Contract
0x38 Read/write Read enabled state; write 1 to start once.
0x3c, 0x40 Read/write, read Final cycle number and compiled period in capture ticks.
0x44 Read/write Reference mode: step 0, ramp 1 or sine 2. Other values are refused.
0x48, 0x4c, 0x50 Read/write Signed Q8.24 reference amplitude, offset and ramp increment.
0x54 Read/write Modulo-16 phase increment, restricted to 0–15.
0x58, 0x5c, 0x60 Read/write Fault kind 0–3, target cycle and duration in periods.
0x64 Read/write Read armed configuration state; write 1 before start to arm one fault. Duration must be positive and target no later than the final cycle.
0x68 Read Bits 0–2: injector ready, actuator freeze and software overload request.
0x6c, 0x70, 0x74 Read Compiled thermal-model flag, miss limit and signed safe actuator value.
0x78, 0x7c Read Fixed-point fractional bits (24) and register ABI version (1).

Arming copies the declared schedule into the actual injector on the accepted capture edge and locks configuration readback to that schedule. Start remains available after arming. Common reset clears enabled/armed state and restores the step reference with amplitude one, zero offset/ramp, phase increment one and final cycle zero. Runtime overload execution is separate from the hardware overload-request level.

FIFO record window and completion

event_record_window.sv prefetches one actual FIFO record and holds it for bus reads. Read 0x80, 0x84, 0x88 and 0x8c for its four words in increasing significance; arbitrary read order is allowed. Write 1 with all byte strobes to 0x94 to consume the held record. Invalid accesses and POP without a held record return SLVERR. Prefetch consumes a FIFO entry into receiver storage; that receiver record remains part of the undrained stream until POP.

Status at 0x90 reports held record, fetch pending, FIFO empty and run drained in bits 0–3. run_drained requires all three storage conditions to be empty and capture quiescence to have crossed four bus synchroniser stages. This delays completion past the FIFO's pointer synchronisers and registered empty calculation. Neither capture completion nor FIFO empty alone proves the stream has drained. Reset clears receiver and completion state.

Simulation tests read and POP actual records through the combined AXI top, bind the binary drain to source/simulator hashes and send it through the public host analyzer. Resulting reports remain simulation_only, with no processor timing, power or physical CDC claim.

Software run reset

Bus-local 0x98 controls the run banks. Write 0 with all byte strobes to assert reset, then write 1 to release it. Assertion is permitted only while the run is disabled or finished; an active run's deadlines cannot be erased by software reset. Invalid data, partial writes and repeated release while already enabled return SLVERR without changing state.

Read bits 0–3 for bank enabled, capture ready, bus ready and reset assertion permitted. Poll bits 0–2 until all three are set before configuring a fresh run. Capture readiness is registered after local reset release and then synchronised into the bus domain; a stopped capture clock cannot report ready. Holding bank reset makes run-register accesses invalid, while the local reset register remains accessible.

Bank reset flushes plant, monitor, injection, configuration, sample/time snapshots, FIFO and receiver state in both domains. It preserves AXI channel state and the request mailbox, so an already accepted read response or reset write response remains valid under backpressure. Consume responses from the previous run before using a new run's data. Resetting an unconsumed receiver record discards that run's remaining stream; drain and save it first when retaining the run's evidence.

Retained processor interrupt

retained_interrupt.sv turns capture IRQ events into a retained bus-domain level. Its 64-bit generation counter increments once per capture edge containing sample interrupt, the first safe indication or the first run-finished indication. Simultaneous sources coalesce. Persistent safe/finished levels do not repeatedly increment it. The counter outlasts a run with a 32-bit final cycle number; it resets with the common run banks.

Offset Access Contract
0x9c Read Return current generation's low word and snapshot both words.
0xa0 Read Return the snapshot's upper word; refused before a low-word observation.
0xa4 Write Write 1 with all strobes to acknowledge the observed generation and consume its snapshot credit. Missing credit, partial writes or other data are refused.
0xa8 Read Bits 0–1: interrupt pending and snapshot valid.

interrupt_line stays asserted until the observed generation is acknowledged. A newer event remains pending when software acknowledges an older snapshot. An event still in the synchroniser pipeline reasserts the level when it reaches the bus domain. Acknowledging the IRQ does not clear the independent safe latch. Read the existing capture status to inspect safe/finished state. The Gray counter uses two bus synchroniser stages; physical skew and maximum-delay constraints must be qualified before board use. These simulations do not verify kernel IRQ handling.

Fixed-point plant

Signed Q8.24 means raw integer divided by 2^24, range [-128, 128−2^-24]. A product is signed 64-bit; three products accumulate in signed 66-bit precision. Arithmetic right shift by 24 rounds toward negative infinity. Saturation occurs once at the state/output boundary. Both mechanical states update from their old values together; intermediate states are not rounded.

The mechanical model is m*x'' + c*x' + k*x = u, with state [x, v] and continuous matrix Ac = [[0, 1], [-k/m, -c/m]], input vector Bc = [0, 1/m]. Zero-order hold gives Ad = exp(Ac*T) and Bd = integral(exp(Ac*t)*Bc, t=0..T). The systemID author's mechanical example describes this discretisation; our default uses its unit-mass normalization. For the default m=c=k=1, T=0.001, set alpha=0.5, beta=sqrt(0.75), C=exp(-alpha*T)*cos(beta*T), S=exp(-alpha*T)*sin(beta*T)/beta. Then:

Ad = [[C + alpha*S, S], [-S, C - alpha*S]]
Bd = [1 - C - alpha*S, S]
x_next = A00*x + A01*v + B0*u
v_next = A10*x + A11*v + B1*u

The thermal model is theta' = (-theta + gain*u)/tau relative to ambient. With tau=gain=1, T=0.001, its coefficients are A=exp(-T), B=1-exp(-T). These are normalized emulator parameters, not fitted physical plant measurements. Coefficients round to nearest raw integer (ties to even):

Parameter Raw Q8.24 default
A00 16777208
A01 16769
A10 -16769
A11 16760439
B0 8
B1 16769
THERMAL_A 16760447
THERMAL_B 16769

The default quantized models are stable; arbitrary supplied coefficients are the run owner's responsibility and must be documented and checked for representability and stability. For a 2×2 real discrete matrix, check the strict Jury inequalities 1−det>0, 1−trace+det>0, 1+trace+det>0; thermal requires abs(A)<1. Saturation makes the emulator nonlinear and must be reported with sample clipping flags.

The plant uses the actuator present strictly before the sample edge. A command on that edge updates the actuator for the following sample. Mismatched-cycle or exact-deadline commands increment late_commands; the first such accepted command in an observed cycle produces ACT_LATE (code 13). It cannot fulfil that cycle's deadline. Event cycles identify the observation cycle, including the new cycle on a boundary edge; the command's original tag remains on the command port. Frozen or safe-state writes are ignored. Multiple commands may update the same register, so the latest accepted value is used; this is not a command queue.

Step produces offset plus amplitude. Ramp uses an initially zero, saturating Q8.24 accumulator, incremented after each sample, then multiplied by amplitude and offset. Sine uses sixteen uniform phase samples of sin(2*pi*phase/16), independently rounded to Q8.24. It advances once per sample; no interpolation or analog waveform fidelity is claimed. Reference multiply and add use wide signed arithmetic and saturate only after scaling.

Deadline, safe state and injected faults

A missing timely write at a deadline increments total and consecutive misses; a fulfilled deadline clears the consecutive counter. Reaching MISS_LIMIT applies SAFE_VALUE on that edge, latches safe_interrupt and captures SAFE_STATE. Safe application wins over command writes, freeze and the simultaneous plant update. Only the common run reset clears the latch. FAULT_DETECTED is captured at this trip when an injection is pending. Ordinary misses do not invent an injected-fault detection. SAFE_STATE and FAULT_DETECTED share the trip timestamp.

One schedule can be armed per run. Arms while busy/used, zero-duration arms, past targets and targets beyond the last sample are refused. Arming must precede the sample edge; the data is latched, so subsequent input changes cannot replace the schedule. A trip suppresses subsequent ordinary sample IRQs and prevents further injections; an already pending delayed IRQ can still release. Reset is the rearm boundary.

The delay-service test waits for the saved delayed IRQ and does not service intervening normal IRQs. This stimulus yields two missed periods and a monitor trip at the release. With period 100,000 and threshold two, injection-to-detection is exactly 200,000 ticks, and first-missed- deadline-to-safe-state is 100,000 ticks. These are simulation invariants, not board statistics.

Simultaneous capture and losses

control_event_capture.sv snapshots all eight supported control strobes, each cycle tag and a single free-running 64-bit counter value before serialization. Accepted groups retain that value through the stream. Within a group, old-cycle events precede new-cycle events; equal cycles sort by code. Groups retain capture order. ACT_LATE is optional in the domain snapshot; archived snapshots and record format v1 remain unchanged.

The default queue holds 64 groups. Each head emits one record per capture edge. Queue-full rejects the newest complete group and counts its set bits; a full downstream FIFO drops and counts each serialized record. Both contribute once to a saturating 32-bit overflow_count. Any loss invalidates the host run. No source is stalled and no dropped event is recreated. The FIFO uses the existing common-reset CDC contract. Neither group serialization nor RAM inference establishes a 100 MHz board timing result.

Reproduce

Native AXI simulation process

make axi-simulator SIMULATION_THERMAL=0 builds the mechanical production top; select 1 for the thermal plant. The executable is build/axi_simulator_0/axi_simulator or build/axi_simulator_1/axi_simulator. These models use a 32768-tick period, a 256-record FIFO, a 16-group capture queue, 5 ns capture half-period and 7 ns bus half-period. No vendor IP is used.

The process accepts decimal request lines on stdin and flushes one response,value,simulation_nanoseconds reply on stdout:

Request Effect
R address Actual AXI register read; reply retains its RRESP and data
W address data strobes Actual AW/W/B transaction; reply retains BRESP
T nanoseconds Advance both simulated clocks
I nanoseconds Advance until retained IRQ or the bounded wait expires; value is IRQ level
Q Finalize and exit without a reply

Address, data and strobe bounds are 255, 4294967295 and 15. Advance/wait requests are bounded to 10000000 ns, each AXI transaction to 100000 ns. Invalid process requests fail before access; aligned register permissions and SLVERR come from the production RTL decoder. EOF also finalizes the process. Reset starts both clock domains; software must poll register 0x98 after a later bank release.

Clocks advance only during requests. Host calculation and pipe waiting consume no simulated time; callers must explicitly advance time to model delay. This transport exercises actual CDC, plant, monitor and FIFO state. It does not establish Linux scheduling latency, UIO/kernel IRQ behavior, physical CDC or power.

tests/test_axi_simulator.py streams live sample snapshots to each public C/Rust PID/LQR executable and submits the returned commands through AXI. Both plant modes retain matching command/plant histories, original read-edge timestamps and 32768-tick sample/deadline cadence through the event receiver.

.venv/bin/pytest -q tests/test_axi_simulator.py

Linux UIO transport

make uio-transport builds build/uio_transport. It accepts explicit arguments uioN name version map physical_address_decimal followed by the same stdin R/W/T/I/Q protocol. Name, version, sysfs map identity and /dev/uioN major/minor must match before access. Only the uio_pdrv_genirq platform driver is accepted; the tool does not bind devices, load drivers or choose an aperture automatically.

The selected map uses map * page_size as its mmap offset, then adds the sysfs offset to the returned pointer. For this driver, the declared physical register address must equal the page-aligned sysfs addr plus offset. The page-rounded map size must contain the entire 256-byte aperture. The tool verifies map metadata again after mmap, requires ready run banks and reads register ABI version 1 before serving requests. These rules follow the Linux UIO HOWTO and the generic platform driver.

Accesses are single volatile little-endian 32-bit loads/stores with RV64 fence iorw,iorw or x86_64 full barriers. Partial strobes and unaligned offsets are refused before access. UIO does not return AXI response signals: response zero means the CPU access completed, and response two is a local refusal. Callers must respect the documented register permissions and state; an invalid remote access may produce a CPU bus fault rather than a recoverable SLVERR reply.

I re-enables the generic driver with a native-endian signed 32-bit value 1, waits with ppoll and reads exactly four bytes of cumulative UIO interrupt count. The in-process API retains that count independently of the RTL IRQ generation. A false result means timeout. The caller must ACK the observed RTL generation before its next wait; ACK never resets the kernel counter. T sleeps while hardware keeps running. Reply time is absolute monotonic host nanoseconds, separately identified from both fabric ticks and simulator time.

UioDevice is also available to an in-process native controller. Ownership uses a nonblocking advisory file lock, so all cooperating users must take that lock. Close unmaps the aperture and closes the descriptor; it disables IRQ only after this instance has successfully managed IRQ. It never resets an active run. No board is available: builds and genuine public-entry refusal tests currently cover this adapter. Successful hardware mmap, MMIO, kernel IRQ delivery, RV64 cross-compilation and board acceptance are still unverified.

.venv/bin/pytest -q tests/test_uio_transport.py tests/test_axi_simulator.py

Native run controller

make run-simulation SIMULATION_THERMAL=0 or 1 builds build/run_simulation_0/run_simulation or its thermal counterpart. Invoke it with configuration events.bin tracking_raw.csv. It links the actual C PID/LQR kernel directly into the production RTL model. make run-uio builds build/run_uio, which accepts the same first three arguments followed by uioN name version map physical_address_decimal and uses the same run lifecycle with direct in-process MMIO. Successful UIO operation is not yet board-qualified. make run-amp-uio builds the separate Linux AMP logger, which drains firmware telemetry and fabric events after the dedicated controller arms. Its resource configuration names both IRQ-free maps explicitly; Linux does not write controller commands or acknowledge the dedicated hart interrupt.

The simulation transport advances its context one nanosecond at a time. It evaluates inputs before sampling the next bus edge, toggles the 7 ns/5 ns half-period clocks, and evaluates again when a clock changes. This production RTL has no delayed processes or time-dependent HDL expressions; an unchanged-clock step does not need that second evaluation. Input-before-clock ordering follows the Verilator evaluation guidance. Reference comparisons preserve byte-identical events, raw tracking and summaries for both plants, PID/LQR, different references and injected freeze/overload cases. This is simulation parity, not physical timing or processor performance evidence.

Configuration is whitespace-separated, with every field required in this order:

pid 32 32768
33554432 16777 8388608 4194304 33554432 16777216 50331648 -67108864 67108864 -33554432 33554432
0 16777216 0 16777 1
none 0 0
0 0

The rows supply controller (pid/lqr), cycle count and expected compiled period; eleven coefficients in the native controller API order; reference mode, amplitude, offset, ramp and phase; fault kind (none, drop, delay, freeze, overload), target cycle and duration; overload work iterations and modeled overload nanoseconds. Raw reference and controller fields use signed Q8.24. None requires zero target and duration. Overload work is an actual volatile sum of squared indices, recorded in the raw trace. Modeled delay advances RTL time and is rejected by run_uio; host calculation alone advances no simulated time. The physical path can execute work iterations with modeled delay zero.

The controller refuses reset of active runs or unread previous records, then polls bank readiness, checks ABI/Q format/compiled period and configures before START. Each retained IRQ observation snapshots its generation, reads actual sample metadata, computes a native command, stages/commits it and ACKs only the observed generation. Safe/finished status vetoes command submission independently of kernel output. Raw tracing preserves submitted status; a register commit is not proof that the monitor accepted the actuator value during a freeze. A single modeled 500000 ns overload crosses one 32768-tick period: the actual AXI submission can succeed while the independent witness records ACT_LATE and one miss without entering safe state. Tests exercise this distinction on both plants with PID and LQR and replay commands through C and Rust.

The run waits for configured final-cycle completion, producer quiescence and receiver drain. Safe latch does not end the configured run: misses can continue after the third miss first trips safe. Final live counters come from 0x30 and 0x34, not stale sample metadata. Overflow makes the executable fail. Event output is the original 16-byte little-endian FIFO record. Tracking stores only observed samples, raw kernel state, original capture ticks and IRQ generation; dropped IRQs do not create invented tracking rows. Outputs are created exclusively; failed runs retain partial files and existing files are never overwritten. The public output API refuses event/sample writes after completion and repeated completion calls, retaining the already closed files. The tracking header is flushed and checked before software run-bank reset/configuration and START. A header write failure leaves the new event file empty. This checks initial write readiness, not durable storage or future free space. Later event, tracking, close or summary write failures still fail the run and retain partial evidence. The native tests use real child-only file-size limits and /dev/full; they do not replace the output streams. Active drain batches contain at most eight records before returning to IRQ service; final drain repeats batches until the actual receiver reports completion. Completion timeout covers the full configured cycle count and compiled period at the target 10 ns tick, plus one second of margin. Configurations that overflow this unsigned nanosecond timer are refused before starting. Safe IRQ silence does not shorten a run; a physical clock still requires the board acceptance check.

The simulation tests cover both plants, both kernels, all references and all fault kinds. Every recorded controller transition is replayed through the actual C and Rust streaming CLIs. The native entry accepts optional --metadata file for exclusive configuration and completion metadata. The host capture command compiles a frozen source snapshot, binds its executable and original outputs, and regenerates the host reports with explicit observed tracking coverage. PAC1934 logging and physical UIO qualification remain outstanding.

.venv/bin/pytest -q tests/test_native_run.py

Fabric and host report integration

.venv/bin/pytest -q tests/test_control_plant_witness.py tests/test_control_faults.py
yosys -s rtl/check_control_equivalence.ys
verilator --lint-only --Wall --top-module control_plant_witness rtl/*.sv

Tests exercise both plants against exact integer transitions and an independent analytic step response, signed actuator changes, references, saturation, healthy and four injected scenarios, exact-deadline and repeated stale commands, simultaneous timestamps, queue wrap, counted losses and reset. The host command verifies the hash-bound RTL sources, executable and tracking series. Power is explicitly absent, so those reports cannot qualify complete board evidence.

The equivalence script compares each prepared component with opt -full (word-level arithmetic), including both plant modes, cycle registers and a two-group capture queue. It checks optimization semantics component by component. The integrated wrapper is exercised through public-port RTL-to-host tests; a monolithic technology-mapped system proof has not been completed. This does not qualify a vendor netlist, physical CDC, RAM mapping or place-and-route.

Native Linux scheduling

run_simulation, run_uio and run_amp_uio accept --cpu N, --scheduler normal|fifo and --priority N, in any order after the positional arguments. The simulation capture command forwards the same options. Without them, the run inherits its calling thread's scheduler and allowed CPU set. normal means Linux SCHED_OTHER, priority zero. fifo requires an explicit allowed CPU and priority within the kernel's FIFO range. Requested CPU selection narrows the inherited set; it cannot widen a cpuset.

The runtime applies and reads back the policy before acquiring the device or opening raw outputs. A rejected request fails the run; it never falls back silently. Only the calling run thread is changed. Parent processes, kernel IRQ threads and other services retain their own policies. Affinity does not reserve or isolate a CPU.

Native metadata contains host_policy: requested CPU/scheduler/priority (minus one means inherited), actual kernel scheduler and priority, the complete allowed CPU list, observed CPU and nice value read immediately after applying the request. These are startup facts, not a measurement of scheduling latency or proof of a real time kernel. Later external policy/CPU changes are outside this startup snapshot.

build/run_simulation_0/run_simulation configuration.txt events.bin tracking_raw.csv \
  --metadata native_metadata.json --cpu 0 --scheduler normal

CPU zero is an example; select an actual CPU from the process's inherited allowed set. FIFO permission depends on the kernel's capabilities and resource limits. See the Linux sched_setaffinity and sched_setscheduler interfaces. Hardware processor timing and physical acceptance remain unqualified.

Native FIFO loss qualification in simulation

make run-simulation SIMULATION_FIFO_ADDRESS_BITS=1 compiles a two-record FIFO. RUN_SIMULATION_DIRECTORY selects a distinct build directory when preserving other simulator variants. Default native builds retain 256 records. The public capture producer binds the compile parameters, retains actual native completion counters and reports declared FIFO loss as invalid. Live monitor misses are distinct from misses inferred from an incomplete event stream; a dropped actuator record cannot establish a real missed deadline.