Safety Analysis — SCPN Phase Orchestrator

SPDX-License-Identifier: AGPL-3.0-or-later Commercial license available

Safety analysis for Kuramoto-based oscillator control in industrial settings.


1. Scope

This document covers the safety-relevant properties of the SCPN Phase Orchestrator when deployed as a supervisory control layer for coupled oscillator systems. Target domains include plasma stabilisation (tokamak), power grid synchronisation, and neuromorphic process control.

Applicable standards:

Standard Scope
IEC 62443 Industrial automation security (zones, conduits, SL targets)
NERC CIP Critical infrastructure protection (bulk electric systems)
IEC 61508 Functional safety (SIL classification)
IEC 61511 Safety instrumented systems (process sector)

2. Hazard Analysis

2.1 Identified Hazards

ID Hazard Cause Severity Likelihood
H-1 Loss of synchronisation Coupling gain (K) exceeds stability boundary High Medium
H-2 Unbounded control action ActionProjector bounds misconfigured High Low
H-3 Regime misclassification Order parameter R corrupted or delayed Medium Medium
H-4 Stuck in Critical regime Cooldown prevents recovery transition Medium Low
H-5 TLS credential compromise Modbus adapter certificate leak High Low
H-6 Rate-limit violation Control output changes faster than actuator can track High Medium

2.2 Hazard Mitigations

Hazard Mitigation Implementation
H-1 STL runtime monitor: always (R >= 0.3) monitor/stl.py with rtamt
H-2 ActionProjector value clamping spo-supervisor/projector.rs
H-2 Kani formal proof of clamp correctness spo-supervisor/src/formal_safety.rs
H-3 Hysteresis and hold-step filtering spo-supervisor/regime.rs
H-4 Critical always bypasses cooldown RegimeManager::transition()
H-5 Mutual TLS with certificate validation adapters/modbus_tls.py
H-6 Rate-limit enforcement in ActionProjector spo-supervisor/projector.rs

3. Safety Requirements

3.1 Control Bounds (SR-1)

All control actions output by the ActionProjector shall satisfy:

lo <= action.value <= hi

for the configured bounds (lo, hi) of each Knob. This is enforced by project_value() in the Rust kernel and verified by Kani proof action_projector_value_clipping_contract.

Status: Verified by crate-owned Kani harness (unit tests pass; CI fails on proof failure)

3.2 Rate Limiting (SR-2)

The absolute change in any control output between consecutive steps shall not exceed the configured rate limit:

|action(t) - action(t-1)| <= rate_limit

The floating supervisor path enforces this in ActionProjector::project(). Certification-oriented actuator paths use the exact fixed-point helpers compute_adaptive_rate_limit_fixed() and project_fixed_point_value(), where the adaptive limit is bounded by:

min_limit <= rate_limit(t) <= max_limit

and the projected actuator movement satisfies:

|action(t) - action(t-1)| <= rate_limit(t)

Kani proofs: adaptive_rate_limit_contract and action_projector_adaptive_fixed_point_rate_limit_contract.

Status: Verified for the adaptive fixed-point actuator contract (floating path covered by unit tests; CI fails on proof failure)

3.3 Regime FSM Ordering (SR-3)

The RegimeManager shall never transition directly from Critical to Nominal. The path must pass through Recovery:

Critical -> Recovery -> Nominal

This prevents abrupt removal of safety interlocks. Kani proof: critical_never_evaluates_directly_to_nominal.

Status: Verified by crate-owned Kani harness (unit tests pass; CI fails on proof failure)

3.3.1 Nominal Safe Envelope (SR-3a)

From a Nominal current regime with no hard boundary violations, a finite mean coherence summary satisfying:

R_CRITICAL <= mean_R <= 1.0

shall not classify directly as Critical. The verified proof harness is nominal_safe_summary_never_classifies_critical.

Coupling-bounds guarantees are enforced at the action-projection layer. A full continuous-time proof that bounded K preserves the coherence premise for every oscillator topology remains a separate Lyapunov/reachability task.

Status: Verified for the discrete supervisor classification contract

3.4 Critical Bypass (SR-4)

Transition to Critical regime shall always succeed, regardless of cooldown state. Safety-critical state changes must never be delayed.

Status: Verified by unit tests; Kani transition-state proof remains future work

3.5 Transition Log Bounded (SR-5)

The transition log shall never exceed MAX_LOG_LEN (100) entries. Unbounded growth would constitute a memory safety violation in long-running deployments.

Status: Verified by unit tests; Kani bounded-log proof remains future work

3.6 TLS Authentication (SR-6)

All Modbus connections to SCADA endpoints shall use TLS mutual authentication. Plaintext Modbus TCP is not permitted in production deployments (IEC 62443 SL-2+).

Status: Implemented (adapters/modbus_tls.py), not yet penetration-tested

3.7 STL Runtime Monitoring (SR-7)

Deployed systems shall run continuous STL monitoring of the order parameter R and coupling gain K against their safety specifications. Violation (negative robustness) shall trigger an immediate regime transition to Critical.

Status: Implemented (monitor/stl.py), integration with supervisor pending


4. Verification Methods

4.1 Currently Verified

Property Method Location
Value clipping correctness Kani harness + function contract + Lean fixed-point proof + unit tests formal_safety.rs, projector.rs, formal/lean/SPOFormal/Projector.lean
Adaptive fixed-point rate limiting correctness Kani harness + function contract + Lean fixed-point proof + unit tests formal_safety.rs, projector.rs, formal/lean/SPOFormal/Projector.lean
Nominal safe-envelope classification Kani harness + function contract + Lean fixed-point proof + unit tests formal_safety.rs, regime.rs, formal/lean/SPOFormal/Regime.lean
Critical never evaluates directly to Nominal Kani harness + function contract + Lean fixed-point proof + unit tests formal_safety.rs, regime.rs, formal/lean/SPOFormal/Regime.lean
Degraded-band classification from Nominal Kani harness + Lean fixed-point proof + unit tests formal_safety.rs, regime.rs, formal/lean/SPOFormal/Regime.lean
PHA-C finite-horizon kinematic merge-window bounds Lean fixed-point proof + smoke instantiation formal/lean/SPOFormal/Kinematic.lean, formal/lean/test/KinematicTest.lean
Cooldown bypass for Critical Unit tests regime.rs tests
Log boundedness Unit tests regime.rs tests
Boundary observer triggers Unit tests tests/test_supervisor_regimes.py
Hysteresis correctness Unit tests + property tests tests/test_regime_hysteresis.py

4.2 Not Yet Verified

Property Required Method Estimated Effort
Full Lyapunov stability of coupled Kuramoto under bounded K Mathematical proof + numerical validation Major research effort
Nonlinear stability under parameter perturbation Bifurcation analysis (continuation methods) Medium
Real-time deadline guarantees WCET analysis on target hardware Medium
TLS implementation security Penetration testing, certificate rotation testing Medium
STL monitor integration with supervisor Integration tests with supervisor loop Low
Multi-domain coupling stability Cross-domain Lyapunov analysis Major research effort
Kani proof for transition-log boundedness on actual VecDeque state Kani harness over RegimeManager::transition Low
Kani proof for cooldown bypass on actual RegimeManager state Kani harness over RegimeManager::transition Low

4.3 Kani Integration Plan

The Kani proof harnesses live in spo-kernel/crates/spo-supervisor/src/ and are compiled with cfg(kani). To run them:

cd spo-kernel
cargo kani -p spo-supervisor -Z function-contracts

The GitHub Actions Kani workflow runs the same harnesses and no longer marks proof failures as allowed failures.

4.4 Lean Integration Plan

The Lean proof lane lives in formal/lean/ and mirrors discrete fixed-point supervisor and PHA-C kinematic contracts independently of the Rust/Kani implementation. To run it:

cd formal/lean
lake build

The GitHub Actions Lean workflow builds the Lake project whenever Lean proofs, projector contracts, regime-classification contracts, or kinematic proof templates change. The Lean lane is not a continuous-time Kuramoto stability proof; it proves the integer/fixed-point contract boundary for projection, finite-input regime decisions, finite-horizon relative-distance budgets, and phase-plus-spatial merge-window lock predicates. Callers must still justify the fixed-point unit conversion and step-bound assumptions for each physical domain.


5. IEC 62443 Compliance Notes

Zone Model

The Phase Orchestrator operates as a Level 2 (supervisory control) component. Modbus/TLS connections to Level 1 (basic control) devices must traverse a conduit with:

  • SL-2 minimum: authentication, integrity, confidentiality
  • Certificate-based mutual TLS (implemented in modbus_tls.py)
  • Network segmentation enforced by external firewall rules (not in scope)

Security Levels

Requirement SL-1 SL-2 SL-3 Status
Unique user identification -- Yes Yes Implemented (TLS cert CN)
Integrity of communicated data -- Yes Yes Implemented (TLS)
Data confidentiality -- -- Yes Implemented (TLS encryption)
Audit trail Yes Yes Yes Implemented (audit/ subsystem)
Denial-of-service resistance -- -- Yes Not yet addressed

6. NERC CIP Applicability

For bulk electric system deployments, the following CIP standards apply:

  • CIP-005: Electronic Security Perimeters — Modbus/TLS satisfies the encrypted communication requirement for routable protocols.
  • CIP-007: System Security Management — patch management and malware prevention are out of scope for the orchestrator itself.
  • CIP-010: Configuration Change Management — the audit subsystem and transition log support change tracking requirements.
  • CIP-013: Supply Chain Risk Management — SBOM generation via CI (wheels.yml) and REUSE compliance address provenance.

7. Revision History

Date Version Change
2026-03-21 1.0 Initial safety analysis